INOVANCE Hata Kodları

311 kayıt
E15.02 INOVANCE MD500-PLUS VFD

External fault (NC)

Olası Nedenler
  • External fault signal input to DI terminal (normally closed)
Çözüm
  • Rectify external fault; ensure mechanical condition allows restart (F8-18)
E16.01 INOVANCE MD500-PLUS VFD

Modbus communication fault

Olası Nedenler
  • Modbus communication timeout
Çözüm
  • Ensure proper RS485 wiring
  • Ensure proper settings of FD-04 and PLC communication cycle
E16.11 INOVANCE MD500-PLUS VFD

CANopen communication fault

Olası Nedenler
  • CANopen communication timeout
Çözüm
  • Ensure proper CAN cable connection
  • Check values of FD-15 to FD-17; eliminate interference
E16.12 INOVANCE MD500-PLUS VFD

CANopen PDO mapping fault

Olası Nedenler
  • Inconsistency between configured CANopen PDO mapping and actual mapping
Çözüm
  • Check PDO mapping of parameters in group AF
E16.21 INOVANCE MD500-PLUS VFD

CANlink heartbeat timeout

Olası Nedenler
  • CANlink heartbeat timeout
Çözüm
  • Ensure proper CAN cable connection
  • Check values of FD-15 to FD-17; eliminate interference
E16.22 INOVANCE MD500-PLUS VFD

CANlink station number conflict

Olası Nedenler
  • CANlink station number conflict
Çözüm
  • Change FD-13 to make station numbers different
E160.1 INOVANCE MD520 VFD

Modbus communication fault

Olası Nedenler
  • Modbus communication timeout
Çözüm
  • Check RS-485 communication cable connection
  • Check settings of FD-04 and PLC communication cycle
E161.1 INOVANCE MD520 VFD

CANopen communication fault - timeout

Olası Nedenler
  • CANopen communication timeout
Çözüm
  • Check CAN communication cable connection
  • Check parameters FD-15 to FD-17
E161.2 INOVANCE MD520 VFD

CANopen communication fault - PDO mapping

Olası Nedenler
  • Inconsistency between PDO mapping configured for CANopen and actual mapping
Çözüm
  • Check PDO mapping of parameters in group AF
E162.1 INOVANCE MD520 VFD

CANlink communication fault - heartbeat

Olası Nedenler
  • CANlink heartbeat timeout
Çözüm
  • Check CAN communication cable connection
  • Check parameters FD-15 to FD-17
E162.2 INOVANCE MD520 VFD

CANlink communication fault - station conflict

Olası Nedenler
  • CANlink station number conflict
Çözüm
  • Modify CAN station numbers using FD-13
E164.1 INOVANCE MD520 VFD

Master-slave control communication fault

Olası Nedenler
  • Master-slave control communication fault
Çözüm
  • Check communication of expansion card
E17.00 INOVANCE MD500-PLUS VFD

Contactor fault

Olası Nedenler
  • Abnormal driver board and power supply
  • Abnormal contactor
  • Abnormal lightning protection board
Çözüm
  • Replace driver board or power supply board
  • Replace contactor
  • Replace lightning protection board
E18.00 INOVANCE MD500-PLUS VFD

Current sampling circuit damaged

Olası Nedenler
  • Abnormal AC drive current sampling
Çözüm
  • Power on main circuit
  • Contact Inovance if Hall sensor or sampling circuit damaged
E19.02 INOVANCE MD500-PLUS VFD

Motor auto-tuning fault - pole position

Olası Nedenler
  • Fault in auto-tuning on magnetic pole position angle of synchronous motor
Çözüm
  • Ensure motor is connected and there is no output phase loss