INOVANCE Hata Kodları

311 kayıt
E045.1 INOVANCE MD520 VFD

Motor overtemperature

Olası Nedenler
  • Loose connection of temperature sensor
  • Overhigh motor temperature
  • Excessively low overtemperature protection threshold (F9-57 or F9-76)
Çözüm
  • Check temperature sensor wiring
  • Decrease carrier frequency or take cooling measures
  • Raise motor overtemperature protection threshold to 90-100C
E045.2 INOVANCE MD520 VFD

Motor pre-overtemperature

Olası Nedenler
  • Loose connection of temperature sensor
  • Overhigh motor temperature
  • Excessively low pre-overtemperature protection threshold (F9-58 or F9-77)
Çözüm
  • Check temperature sensor wiring
  • Decrease carrier frequency or take cooling measures
  • Raise motor pre-overtemperature protection threshold
E047.3 INOVANCE MD520 VFD

STO fault - undervoltage/overvoltage

Olası Nedenler
  • STO circuit undervoltage or overvoltage
Çözüm
  • Contact technical support
E047.4 INOVANCE MD520 VFD

STO fault - input subsystem exception

Olası Nedenler
  • STO circuit input subsystem exception
Çözüm
  • Contact technical support
E05.00 INOVANCE MD500-PLUS VFD

Overvoltage during acceleration

Olası Nedenler
  • High input grid voltage
  • External force driving motor during acceleration
  • Inappropriate overvoltage suppression
Çözüm
  • Adjust voltage to normal range
  • Cancel external force or install braking resistor; adjust F3-26 to 5-15 Hz
  • Enable overvoltage suppression (F3-23); adjust F3-22 to 700-770V; F3-24 to 30-50
E051.1 INOVANCE MD520 VFD

Pole position auto-tuning error

Olası Nedenler
  • Output phase loss on motor
Çözüm
  • Connect motor output correctly; ensure output contactor is closed
E056.9 INOVANCE MD520 VFD

Output phase loss

Olası Nedenler
  • Motor output phase loss
Çözüm
  • Make sure motor is connected properly and output contactor is normal