E010.1
INOVANCE MD520 VFD
AC drive overload

⚠ Olası Nedenler

  • Excessive load or locked-rotor
  • High carrier frequency
  • Low bus voltage during high speed running with heavy load
  • Derating at low frequency
  • Output grounding
  • Output phase loss
  • Motor parameter error
  • Flying start not applied when motor started during rotation
  • Encoder direction error
  • AC drive model setting error
  • Inadequate power rating

✓ Çözüm Adımları

  • Reduce load; check motor and mechanical conditions
  • Decrease carrier frequency
  • Increase input voltage; enable overmodulation function
  • Avoid heavy load at low speed or select higher power drive
  • Check for output ground points
  • Check for output phase loss
  • Check motor nameplate parameters and perform auto-tuning
  • Enable flying start (F6-00)
  • Change encoder A/B phase sequence (F1-30)
  • Set AC drive model correctly
  • Replace with higher power drive